Workflows / Sizing cables: current, voltage drop and grouping
Sizing cables: current, voltage drop and grouping
How a cable is sized: the design current and its protective device, the current-carrying capacity once corrected for grouping, temperature and installation, the voltage drop limits of IEC 60364 and the national rules, the fault check, and the details people forget.
- Available
- Free account
Three checks every cable must pass
A cable is chosen by the largest of three answers: it must carry the design current continuously without overheating, keep the voltage at the far end within the limit, and let the protective device clear a fault fast enough. The smallest cable that passes one check often fails another.
Current-carrying capacity
- Start from the circuit's design current, then the rating of its protective device, which must be at least that current.
- Take the cable's tabulated capacity for its installation method (clipped direct, in conduit, on a tray, buried) from the tables of IEC 60364-5-52 or the national rule.
- Apply the correction factors for ambient temperature, grouping with other loaded circuits, thermal insulation round the cable and, when buried, the soil.
- The corrected capacity must be at least the rating of the protective device.
Voltage drop
Current through a cable's resistance loses voltage along its length. The wiring rules (IEC 60364-5-52 and the national rules built on it, such as BS 7671 or NF C 15-100) set the largest drop allowed from the origin of the installation to the equipment: a tighter limit for lighting than for other uses, and more allowed when the installation has its own substation. The drop is worked out from the cable's resistance and reactance, the current and the length.
Long runs, to a plant room or across a car park, are where voltage drop rather than current sets the size.
The fault check and the cable tray
- The earth fault loop impedance must be low enough for the device to disconnect within the time the rule sets; a long, thin cable can fail this even while it carries its current.
- Cables laid together on a tray are grouped: their number and arrangement lower each one's capacity, and the tray must keep room within the fill its maker or the rule allows, for cooling and for later circuits.
Doing it in the model
When circuits, cable routes and trays are in the model, each cable's length is measured along its real route rather than guessed, and the tray fill follows the cables actually laid on it. Calq sizes cables by voltage drop from their circuits and real routes and reports the tray fill, with every assumption stated; the current-carrying tables of the wiring rules stay the designer's.
Common mistakes
- Lengths measured on plan, ignoring risers and drops.
- Grouping factors forgotten on a crowded tray.
- Voltage drop checked to the board, not to the last outlet.
- Spare room on the tray assumed rather than measured.
Questions
Which voltage drop limit applies?
The one in the wiring rules where you build (IEC 60364-5-52 and its national versions such as BS 7671), measured from the origin of the installation; read the figure in the current edition, since these texts are sold.
Does a larger cable always help?
It lowers the voltage drop and the loop impedance, but takes more room on the tray and in the terminals. Size to the largest of the three checks, not more.
Why measure lengths in the model?
Because the real route climbs risers, drops to equipment and follows trays round obstacles; a plan measurement misses all of it, and voltage drop grows with length.