Workflows / Earthing and lightning protection in a building
Earthing and lightning protection in a building
What earthing and lightning protection each do, the parts of both systems, how IEC 62305 sets an external lightning protection system by its class (mesh, rolling sphere, down conductors), equipotential bonding, and how to model it so the trades build it.
- Available
- Free account
Two systems, one purpose: a safe path to earth
Earthing gives a fault current a low-impedance path, so that the protective device disconnects quickly and touch voltages stay safe. Lightning protection intercepts a strike and carries its current to earth outside the building's fabric. Both meet at the earth termination and both rely on bonding: metal parts that could reach different potentials are connected, so a person never bridges them.
The parts of an earthing system
- The earth electrode: rods, tapes or a ring round the building, or the foundation's own reinforcement used as a foundation earth electrode.
- The main earthing terminal at the intake, where the protective conductors, the bonding conductors and the electrode meet.
- Main bonding of the incoming services (water, gas, structural steel), and supplementary bonding in the rooms where it is required, such as bathrooms.
- Protective conductors run with each circuit to every exposed metal part of the equipment.
Lightning protection by IEC 62305
IEC 62305 (EN 62305 in Europe) starts with a risk assessment (part 2) that decides whether the building needs protection and at which level. Part 3 then sets the external system by its class, from I, the most demanding, to IV.
- Air terminations: rods, conductors or a mesh on the roof. The higher the class, the closer the mesh; the standard's tables set its size for each class.
- The rolling sphere method checks what the air terminations protect: a sphere whose radius the standard sets for each class, smaller for the more demanding classes, rolled over the building, must touch only the air terminations.
- Down conductors spaced round the perimeter at the distance the standard sets for the class, joined to the earth termination; the reinforcement or the steel frame may serve as down conductors where it is electrically continuous.
- Surge protective devices at the service entrances protect the internal systems (part 4).
Modelling it so it gets built
A lightning protection system drawn as notes on a roof plan is the first thing lost between design and site. Modelled as elements, the air terminations, down conductors, test joints and electrodes are dimensioned, scheduled and coordinated with the facade and the roof build-up. In Calq they are laid as elements with their IFC classes, and their lengths and counts come from the model.
Common mistakes
- Down conductors fixed through the waterproofing with no detail.
- Metal roof plant left outside the protected zone.
- Bonding forgotten at the gas and water entries.
- No test joint, so the electrode can never be measured.
Questions
Can the reinforcement act as the down conductors?
Yes, when it is electrically continuous from roof to foundation, and this is designed and tested; IEC 62305-3 describes such natural components.
Does every building need lightning protection?
Not always: the risk assessment of IEC 62305-2, or the national rule where you build, decides.
What is the difference between earthing and bonding?
Earthing connects metal to the earth; bonding connects metal parts to each other so that they stay at the same potential.