Workflows / Room acoustics: reverberation and sound between rooms
Room acoustics: reverberation and sound between rooms
The two questions of building acoustics: how a room sounds (reverberation time, absorption, the Sabine formula) and how much sound passes between rooms (airborne and impact insulation, flanking), with the standards that measure them and the design decisions behind both.
- Available
- Free account
Two different problems
Room acoustics is about the sound inside a room: whether speech is clear in a classroom, or music full in a hall. Sound insulation is about the sound that passes from one room to another through walls, floors and the paths around them. A room can be well insulated and still sound poor, and the other way round.
Reverberation time
Reverberation time T is the time a sound takes to decay by 60 decibels once it stops. Sabine's formula estimates it from the room's volume V in cubic metres and its total absorption A in square metres: T = 0.161 V / A. The absorption is each surface's area times its absorption coefficient, summed over walls, floor, ceiling, furniture and people.
- Large hard rooms reverberate; adding absorption, usually on the ceiling, shortens T.
- Targets depend on use and volume: short where speech matters, in classrooms and offices, longer for music. National rules and guidance set them for each building type.
- Reverberation is measured on site by ISO 3382.
Sound between rooms
- Airborne insulation, for voices and music through a wall or floor, is rated by a single number: Rw in the laboratory, DnT,w between real rooms (ISO 717-1).
- Impact insulation, for footsteps on a floor, is rated by L'nT,w between real rooms (ISO 717-2); a lower number is better.
- Flanking: sound bypasses the separating element through the walls, floors, ceilings and ducts connected to it. ISO 12354 predicts the result in the building from the elements and their junctions.
Design decisions
- Mass and separation: heavier constructions, and doubled ones with an air gap, insulate better.
- Seal every gap: a small opening round a pipe or a door undoes a heavy wall.
- Isolate the floor: a resilient layer under a floating screed cuts impact sound.
- Plan noisy rooms next to noisy rooms, and keep plant away from bedrooms.
With the model
Room volumes, surface areas and their finishes come from the model, so the reverberation time is worked out for every room as the design changes. Calq computes it room by room from the finishes the model holds, and the sound between rooms from each wall's stated rating or its mass, saying which figures it assumed; flanking is left to the acoustician.
Common mistakes
- Calculating with the empty room when people and furniture absorb.
- Checking the separating wall and ignoring flanking through a continuous ceiling void.
- Absorption coefficients taken at one frequency only.
Questions
What is a good reverberation time?
It depends on use and volume; rooms for speech need it short. Use the rules and guidance of your country for that building type.
Does Sabine's formula always work?
It suits rooms with spread-out absorption; for very absorbent rooms the Eyring formula is closer to what is measured.
Is Rw the same as DnT,w?
No. Rw is measured on the element alone in a laboratory; DnT,w is measured between real rooms, flanking included, and is usually lower.